RDS2-630 Bypass Isolation Transfer Switches

Default ATS wiring terminals design is top input and bottom output (load). We provide an option to overturn ATS’s input and output load copper bars, flexible mounting at 250A – 630A. Below pictures to illustrate. Note: If customer need overturned input and output terminals, please specify at ordering.


Below is an example of 630A Automatic Transfer Switch overturned input with output wiring terminals.


Regular 630A ATS terminals


Overturned 630A ATS terminals


Below table shows different types of RDS2 control modules’ features:

Pictures



Model

RDS2-B (Basic)

RDS2-E (Intelligent)

RDS2-F (Fire-fighting)

RDS2-G (For External Control)

Control element

Relay

Chip

Chip

Relay

Power Supply for Controller


AC165V to AC265V 50/ 60Hz

Auxiliary power supply

No

DC24V

DC24V

GA: DC12/24V; GB: Voltage

free signal.

Voltage measuring range

No

40-300V

40-300V

No

Power consumption

≤ 10W

Working positions

Three working positions (I power ON, II power ON, OFF)

Operating mode

Auto, Manual

Auto, Manual, Remote

Auto, Manual

Auto, Manual

Indication

LED

LED + LCD display (optional)

LED

Source priority

Source I

Default source I, with LCD can set priority on

source I/II/no priority.

Per external controller settings, can work with external controller like Deepsea, ComAp, Smarten controllers, etc.

Under voltage protection

No

Default 187V, with LCD can set between 160-200V.

Over voltage protection

No

Default 265V, with LCD can set between 240-290V.

Over/under frequency protection

No

With LCD can set ±20% of its rated frequency.

Engine exciser

No

Yes

No

Transfer delay

No

Default 5s, with LCD can set between 0-300s.

Recovery delay

No

Default 5s, with LCD can set between 0-300s.

Phase lost detect

A,N phase

A, B, C three phase

Generator starter

Yes ( with one set of dry contact)

No

Fire-linkage function

Yes ( Forced 0 position)

Yes (Forced I power, Forced II power, Forced 0)

Switch failure alarm

No

Yes

Mechanical isolation padlock

Yes (0 position padlock function)

RS485 communication

No

Optional

No


New features upgraded on RDS2-E:

1. ATS Transfer to "0" position when I or II power both failure. On the condition that A phase is normal, B or C phase loss, over or under voltage, over or under frequency, note, if A phase loss, this function not available, ATS must have power supply to enable it’s motor operation.

2. Fault event log.

3. Optional L module: Over load (current) protection, need to install additional CT go out of ATS. Threshold settable. This is another cards, please specify at ordering.


  • Reliable mechanical interlock device and electrical interlock protection, avoiding two MCCB closing at the same time; Controller power supply and power source sampling power are separated from SCM control system, effectively overcoming EMI from the hardware design;

  • Controller is removable, and can be installed separately, meet different installation requirement;